hydro-eye acid level monitorHydro-Eye acid level Monitors and Alarms for flooded lead-acid batteries
Probe TypesSelect a probe by battery or probe typeProbe installation instructionsFind or become a Hydro-Eye dealerFrequently Asked Questions about our monitorsLearn more about Hydro-EyeHydro-Eye Home Page
     
Select a Probe
By Battery
By Model
 
   
   
   
 
 
   
   

Select a Hydro-Eye probe by Model
Type 2A: Monitor - Alarm - Alert - Combo
 

Battery Type Used: Industrial

The Type 2A218MR replaces the former HE-2VB-2.1 flooded battery acid level monitor probe.

The unit is installed on the center cell of an industrial battery by replacing the existing vented bayonet cell filler cap.This patented probe is immersed in battery acid to a depth of ½" above the battery plates.

Type 2A Monitor probe

The unit requires a small voltage to operate. This is provided by connecting a black wire from the Monitor to the outboard inter-connecting strap of the adjacent cell in the direction of the battery negative post and a red wire to the outboard strap of the cell on the opposite side. This will provide approximately 6 vdc to the electronics, turning on the LED, but with a current drain of less than 5 milliamperes, much less than the self-discharge of the battery.

The LED is ON at all times, operating in the fail-safe mode. If it is dull, the battery should be charged to prevent sulfation, and if it is out, then the acid level is low and the battery should be charged, then distilled water added. Normally a Monitor on just the center cell will protect the entire battery.

Probe length is 2-1/8"

 

 
 
 
       
       